Sorption dehumidifier DC-50R

  • Stainless steel housing
  • D-MAX sorption rotor
  • Separate guidance of the process and regeneration air
  • Electric PTC regeneration heating
  • Ammeter for regeneration air settings

Specifications/Instructions:

Download Data sheet-DC-50_DE (394 KB)
Download Dimensions-DC-50R (56.83 KB)

Send a request
Dehumidification capacity at 20 ° C and 60% rel. humidity:
3,0 kg/h
Dehumidification capacity at 30 ° C and 80% rel. humidity: 3,2 kg/h
Dehumidification capacity at 10 ° C and 70% rel. humidity: 2,7 kg/h
Dehumidification capacity at 0 ° C and 90% rel. humidity: 2,4 kg/h
Process air flow, nominal, at ext. pressure: 550m³/h, 150Pa
Regeneration air flow, nominal, at ext. pressure: 150 m³/h, 100Pa
Working environment temperature: -20 to +35 °C
Working range humidity: 10 – 100 % rH
El. heater power, max.: 5,0kW
El. motor power, max.: 0,5 kW
El. total consumption, max.: 5,5 kW
Supply voltage: 3x 400V, 50 Hz
Fuse: 20 / 16A
Required switch for remote control (for example, humidistat or remote ON): 10 A
Height (total): 556 mm
Width (total): 556 mm
Deep (total): 578 mm
Weight: 63 kg
Inlet process air: 160 mm
Outlet process air (dry air): 160 mm
Inlet regeneration air: 100 mm
Outlet regeneration air (wet air): 100 mm
Rotor speed: 24 rph
Noise, with associated ducting, 1m free range:
Filter: G3
Field of use and installation Diverse application range, to achieve the lowest relative humidity possible, to dry air to specific value at low temperatures, with wet air exhaust to the outside
Working principle: CONSORB
Installation: Mobile and stationary, standing
Wet air exhaust: Required
Housing: Stainless steel, self-standing
Maintenance accessibility: From the front and from above
Filter: G3 filter for process and regeneration air, easy to reach
Fan: Separate radial fan for process and regeneration air, both fans directly driven
Sorption rotor: D-MAX, d 450mm x h 100mm
Rotor drive: Rotor motor with belt drive and belt tensioner
Regeneration heating: Electrical PTC heater, self-regulating with overheating protection, ammeter for easy reg.-air flow control
Electrical equipment:
All components wired to terminal, On / Off and Man / auto switch, with ammeter, working hour counter and hygrostat socket, standard-configuration
Controlling: Prepared for hygrostat connection
Signal:  Remote-ON/OFF
Supply:
Operating hours counter: Standard
 Device socket: Standard
 Hygrostat/Remote-ON: