Sorption dehumidifier CZ-82 / 102 / 104

  • Aluzinc housing (stainless steel optional)
  • Separate fans for process and regeneration air
  • Washable D-MAX silicagel sorption rotor
  • Also available with steam and gas heater

Specifications/Dimensions:

Download Data sheet-CZ Serie_DE (283 KB)
Download Dimensions-CZ-82 (227 KB)
Download Dimensions-CZ-102 (186 KB)
Download Dimensions-CZ-102L (188 KB)
Download Dimensions-CZ-104 (245 KB)

Dehumidification capacity at 20 ° C and 60% rel. humidity:
25 kg/h
Dehumidification capacity at 30 ° C and 80% rel. humidity:22 kg/h
Dehumidification capacity at 10 ° C and 70% rel. humidity:17,6 kg/h
Dehumidification capacity at 0 ° C and 90% rel. humidity:12,1 kg/h
Process air flow, nominal, at ext. pressure:3.200 m³/h, at 200 Pa ext.
Regeneration air flow, nominal, at ext. pressure:850 m³/h, at 200 Pa ext.
Working environment temperature:-20 to +35 °C
Working range humidity:10 – 100 % rH
El. heater power, max.:30 kW
El. motor power, max.:4,1 kW
El. total consumption, max.:34,1 kW
Supply voltage:3x 400V, 50 Hz
Fuse:63 A
Required switch for remote control (for example, humidistat or remote ON):1 A
Height (total):1905 mm
Width (total):2370 mm
Deep (total):1065 mm
Weight:600 kg
Inlet process air:400 mm
Outlet process air (dry air):400 mm
Inlet regeneration air:250 mm
Outlet regeneration air (wet air):160 mm
Rotor speed:10 1/h
Noise, with associated ducting, 1m free range:
Filter:G3 / F7
Dehumidification capacity at 20 ° C and 60% rel. humidity:
41 kg/h
Dehumidification capacity at 30 ° C and 80% rel. humidity:36 kg/h
Dehumidification capacity at 10 ° C and 70% rel. humidity:28,8 kg/h
Dehumidification capacity at 0 ° C and 90% rel. humidity:19,8 kg/h
Process air flow, nominal, at ext. pressure:5.200 m³/h, at 200 Pa ext.
Regeneration air flow, nominal, at ext. pressure:1.400 m³/h, at 200 Pa ext.
Working environment temperature:-20 to +35 °C
Working range humidity:10 – 100 % rH
El. heater power, max.:50 kW
El. motor power, max.:5,4 kW
El. total consumption, max.:55,4 kW
Supply voltage:3x 400V, 50 Hz
Fuse:100 A
Required switch for remote control (for example, humidistat or remote ON):1 A
Height (total):2105 mm
Width (total):2430 mm
Deep (total):1280 mm
Weight:800 kg
Inlet process air:630 mm
Outlet process air (dry air):400 mm
Inlet regeneration air:400 mm
Outlet regeneration air (wet air):315 mm
Rotor speed:10 1/h
Noise, with associated ducting, 1m free range:
Filter:G4 / F7
Dehumidification capacity at 20 ° C and 60% rel. humidity:
74,1 kg/h
Dehumidification capacity at 30 ° C and 80% rel. humidity:65 kg/h
Dehumidification capacity at 10 ° C and 70% rel. humidity:52 kg/h
Dehumidification capacity at 0 ° C and 90% rel. humidity:35,8 kg/h
Process air flow, nominal, at ext. pressure:8.000 m³/h, at 200 Pa ext.
Regeneration air flow, nominal, at ext. pressure:2.500 m³/h, at 200 Pa ext.
Working environment temperature:-20 to +35 °C
Working range humidity:10 – 100 % rH
El. heater power, max.:95 kW
El. motor power, max.:11,5 kW
El. total consumption, max.:106,5 kW
Supply voltage:3x 400V, 50 Hz
Fuse:200 A
Required switch for remote control (for example, humidistat or remote ON):1 A
Height (total):2105 mm
Width (total):2862 mm
Deep (total):1265 mm
Weight:900 kg
Inlet process air:630 mm
Outlet process air (dry air):296 x 786 mm
Inlet regeneration air:400 mm
Outlet regeneration air (wet air):315 mm
Rotor speed:10 1/h
Noise, with associated ducting, 1m free range:
Filter:G4 / F7
ApplicationsDiverse application range, to achieve the lowest relative humidity possible, to dry air to specific value at low temperatures, with wet air exhaust to the outside
Working principle:CONSORB
Installation:Stationary, standing
Wet air exhaust:Required
Housing:Aluzinc, self standing
Maintenance accessibility:From the front and from the side
Filter:G4-filter cassette for the process air, F7-filter cassette for the regeneration air, quick and easy access
Fan:Separate radial fan for process and regeneration air, both fans directly driven
Sorption rotor:Seibu Giken DMR, d 770mm x h 200mm
Rotor drive:Rotor motor with belt drive and belt tensioner
Regeneration heating:Electrical PTC heater, self-regulating with overheating protection, ammeter for easy reg.-air flow control, seven stages, total 30 kW
Regeneration options:
Steam, hot water, hot water with el. additional heating
Controlling:(0%, 58%, 100% power), optionally step-by-step or linear heating control via 0-10V control signal available
Signals:Remote-ON/OFF, alarm
Power supply:
Operating hours counter::Standard
Device socket::
Hygrostat/Remote-ON: