Sorption dehumidifier Type CS-5
- Stainless steel housing
- D–Max sorption rotor
- Separate guidance of the process and regeneration air
- Electric PTC regeneration heater
- Ammeter for regeneration airflow
Specifications/Instructions:
cs-5-gb (2MB)
Download Dimensions-CS-5_CS-5l (43 KB)
Dehumidification capacity at 20° C and 60% RH:
|
0,35 kg/h |
Dehumidification capacity at 30° C and 80% RH:
|
0,4 kg/h |
Dehumidification capacity at 10° C and 70% RH:
|
0,3 kg/h |
Dehumidification capacity at 0° C and 90% RH:
|
0,2 kg/h |
Process airflow, nominal, ext. pressure: | 65-90 m³/h, free outlet |
Regeneration airflow, nominal, ext. pressure: | 30-50 m³/h, free outlet |
Working environment temperature: | -20 to +35 °C |
Working range humidity: | 10 – 100 % RH |
El. heating capacity, max.: | 0,7-0,85 kW |
El. motor power, max.: | 0,3 kW |
Total power, max .: | 1 kW |
Power supply: | 1x 230V, 50 Hz |
Fuse: | 10 A |
Required current for remote control (e.g., hygrostat or remote ON): | 5 A |
Heght (total): | 270 mm |
Width (total): | 280 mm |
Deep (total): | 338 mm |
Weight: | 9 kg |
Inlet process air: | xx mm |
Outlet process air (dry air): | 80 mm |
Inlet regeneration air: | xx mm |
Outlet regeneration air (wet air): | 50 mm |
Rotor speed: | 36 1/h |
Filter: | G3 |
Working principle: | CONSORB |
Installation: | Mobile and stationary, standing |
Wet air exhaust: | Required |
Housing: | Stainless steel, self standing |
Maintenance Accessibility: | From the front and the side |
Filter: | G3 filters for process air and regeneration air, easy and quick access. |
Fan: | Separate radial fan for the process and regeneration air, both fans directly driven |
Sorption rotor: | D-MAX, d 180mm x h 50mm |
Rotor drive: | Belt driven rotor motor with belt tensioner |
Regeneration heating: | Electric PTC heating, self-regulating and with overheat protection, with ammeter for easy regulation of air flow |
Electrical equipment:
|
All components wired to terminal, On / Off and Man / auto switch, with ammeter and hygrostat socket, standard-configuration |
Controlling: | Prepared for hygrostat connection |
Signal: | Remote-ON/OFF |
Supply: | Safety plug with 2m supply cable |
Operating hours counter: | Optional |
Device socket: | Optional |
Hygrostat/Remote-ON: |